Voltage Drop Calculator

Live

Estimate copper-conductor voltage drop, load voltage, percent loss, and preliminary status from AWG, current, length, and circuit type.

About Voltage Drop Calculator

Use the Voltage Drop Calculator for a preliminary view of voltage lost along a copper conductor run. Enter source voltage, load current, one-way length, copper AWG size, and DC/single-phase or three-phase circuit type. The conductor bench shows estimated volts lost, percent of source voltage, voltage remaining at the load, resistance per thousand feet, circuit-length factor, and approximate power dissipated. A color meter highlights results within 3%, from 3% to 5%, and above 5% for review—not as an approval or conductor-sizing decision.

Estimate conductor voltage drop

Workspace

Structured calculation

Follow the input-to-result path; the fields below remain the source of every value.

Complete the fields to prepare a result.

Nominal voltage at the source; must be greater than zero.

Expected current carried by the conductor.

Distance from source to load, not the round-trip conductor length.

Supported copper American Wire Gauge size.

Select DC/single phase or balanced three phase.

Voltage delivered at load

Enter source, load, conductor, length, and circuit type.

Voltage-drop method

drop volts = circuit factor × current amperes × copper resistance Ω/1,000 ft × one-way feet ÷ 1,000; percent drop = drop volts ÷ source volts × 100; load voltage = source − drop.

How it works

The calculator multiplies load current by conductor resistance and effective circuit length. DC and single-phase circuits use twice the one-way run for outgoing and return conductors; a balanced three-phase estimate uses √3. Resistance varies with conductor material, temperature, installation, and AC effects, so the bundled copper values support preliminary comparisons only.

Examples

50-foot 120 V branch circuit

Example input
{
    "voltage": 120,
    "current": 10,
    "length_ft": 50,
    "wire_gauge": "12",
    "phases": "dc_or_1phase"
}
Expected result
{
    "voltage_drop": 1.588,
    "voltage_at_load": 118.412,
    "voltage_drop_percent": 1.323,
    "resistance_ohms_per_1000ft": 1.588,
    "circuit_factor": 2,
    "status": "within_3_percent"
}

Privacy

This tool does not store your inputs or results on UtilityPages.org.

Citations & sources

  1. Southwire Voltage Drop Calculator

Frequently asked questions

Should I enter one-way or round-trip length?

Enter the one-way distance from source to load. The calculator applies the return-path factor for DC/single phase or √3 for a balanced three-phase estimate.

Does a result under 3% prove the conductor is correctly sized?

No. Voltage drop is only one design consideration. Ampacity, terminals, temperature, bundling, installation method, fault current, protection, equipment requirements, and applicable code must also be evaluated.

Why can field voltage drop differ from this estimate?

Actual resistance changes with conductor temperature and connections, while AC impedance, power factor, load variation, harmonics, and conductor arrangement can affect a real circuit.

Can I use these values for aluminum conductors?

No. The selected resistance table represents copper. Aluminum has different resistance and installation requirements; use a method and data specifically applicable to that conductor.